CASE64 · Manufacturing · Chiller staging program

Distinguishing an eight-to-seven-unit staging change from the broader program result

Historical excess online capacity led to staged operation changes within a real-time utility-efficiency program. The reported 27% intensity improvement reflects combined program activities, not one stopped chiller alone.

01 · CASE ANALYSIS

Installed reserve differs from running reserve

Reliable plant capacity does not require every reserve unit to consume energy continuously. Assess online chiller count and associated pumps against actual cooling demand.

Part-load curves and auxiliary power determine efficient staging rather than a rule that fewer units are always better.

02 · CASE ANALYSIS

Source diagnosis and applied change

Historical 5°C data indicated six analytically required units versus eight running, with source load around 75%.

The actual program later changed operation from eight to seven. The analytical six-unit value is not presented as the achieved operating count.

Diagnosis versus application
StageSource observation
Historical analytical need6 units
Historical actual operation8 units; approximately 75% load
Applied program operation8 → 7 units
Broader reported intensity1.20 → 0.88 kW/RT; approximately 27%
AttributionCombined program activity, not shutdown-only saving

03 · CASE ANALYSIS

Real-time program rather than an isolated switch

The project installed metering and analysis for chillers, CDA and boilers, then progressed to tests and operating guidance.

Unit efficiency, load allocation, operating conditions and poor-performing equipment were reviewed alongside staging.

04 · CASE ANALYSIS

Keep the outcome attribution correct

The program material records eight-to-seven operation and approximately 27% equipment-intensity improvement, with broader records showing 1.20 → 0.88 kW/RT.

These combined results cannot all be credited to one shutdown. Project-wide monetary totals have different dates/scopes and are not assigned as CASE64’s isolated benefit.

Staging review
Decision inputPurpose
Plant RT and unit performance curvesEfficient feasible combinations
Pump/tower auxiliary powerTotal plant boundary
Operating limits and reserveMaintain reliable cooling
Temperature and stable runtimeAvoid unsuitable or unstable staging
Adjusted before/after dataVerify program outcome

05 · CASE ANALYSIS

Operating constraints and verification

Review service temperature, remaining-unit limits, pump flow and reserve before staged reduction. Use hysteresis and adequate runtime conditions when translating tests to controls.

Track total plant intensity over comparable cooling demand and condenser conditions, not only the count of running units.

Source-value comparisons

Distinct stages in the source recordAnalytical need6 unitsInitial running8 unitsApplied running7 units
English chart reconstructed from the published source values; no new measurements or estimates.

Source figures · English edition

Figures correspond to those published in the Korean case. English titles, axes and legends are provided; published values and evidence boundaries are retained. Open a figure at full size to inspect small labels.

Analytical need versus actual chiller count
Analytical need versus actual chiller count

Historical analytical requirement 6, actual running count 8 and mean loading approximately 75%. The program-level 27% result is not attributable to this count comparison alone.

Open full-size figure ↗

APPLY TO YOUR SITE

Connect your operating data to an actionable energy strategy.

Discuss the measurement boundary, data quality, operating constraints and verification approach for your facility.

Discuss your project All English cases