CASE60 · Manufacturing · Chiller additive pilot

Retaining a null result when a chiller-oil additive did not show clear improvement

An oil-fouling hypothesis is tested through actual additive application and before/after operating analysis. The completion report records no demonstrated benefit, providing no basis to assign savings or proceed from an assumed claim.

01 · CASE ANALYSIS

Hypothesis and test objective

The proposed mechanism was that lubricant entering the refrigerant circuit could foul heat-transfer surfaces and an additive might reduce that effect.

This was a project hypothesis. Its physical plausibility does not establish that oil fouling was the actual dominant problem or that the additive worked.

02 · CASE ANALYSIS

Prepare a comparable baseline

Record chiller kW, RT from flow/ΔT, condenser-water conditions, chilled-water setpoint and load factor. Check meter validity and document concurrent cleaning, maintenance or controls changes.

Define the required improvement, measurement uncertainty and observation duration before applying the product.

Pre/post comparison requirements
InputPurpose
kW and delivered RTCooling-normalized performance
Condenser-water conditionsSeparate lift changes
Chilled-water setpoint and load factorMatch operating conditions
Sensor qualityAssess measurement confidence
Concurrent workSeparate additive and other effects

03 · CASE ANALYSIS

Actual project sequence

The source schedule included procurement, analysis/application planning, additive application, efficiency evaluation and a later expansion decision.

Compare kW/RT under comparable conditions rather than lower absolute kW after a load reduction. Other changes may confound apparent efficiency differences.

04 · CASE ANALYSIS

Completion result and decision

The final improvement-item table recorded “no effect” and recognized no separate saving amount. The English interpretation is that the expected improvement was not clearly demonstrated in this field test.

This is not evidence that all additives are ineffective under every condition. It is evidence that this test does not justify assigning a saving or extrapolating an unproven benefit.

Decision record
StageSource status
Oil-fouling prevention ideaImprovement hypothesis
Additive application and evaluationActual project activity
Completion-report effectNo effect recorded
Recognized standalone savingNone
Scope of conclusionThis test and its conditions

05 · CASE ANALYSIS

A reusable pilot protocol

Check test quality even when the result is null: baseline coverage, matched load ranges, sensors, confounding and duration. Document the result for future procurement decisions.

Models may adjust external conditions but should not manufacture an expected benefit. Preserve the gate from hypothesis to field evidence and adopt/decline decisions.