CASE55 · Manufacturing · Chilled-water pump sizing
Re-matching chilled-water pumps to measured flow and head
Actual chilled-water demand and pump operating points are checked against original sizing. Control changes, impeller adjustment and pump replacement are compared at the required service level.
01 · CASE ANALYSIS
Original size versus current demand
Production, pipework and operating patterns can change after installation. A pump that once matched the design may later operate with unnecessary flow, head or throttling.
The source follow-up action was to select 5°C chilled-water pump specifications suited to actual use.
02 · CASE ANALYSIS
Source design and operating records
Representative design specifications for a 2,000 USRT 5°C chiller system were 150 kW motor, 605 m³/h flow and 60 m head.
Different source operating records show approximately 128.9–133 kW at 630 m³/h, and other records show 134 kW at 859 m³/h or 128.9 kW at 760 m³/h. These are different conditions, not a fabricated before/after pair.
| Source record | Power | Flow | Head |
|---|---|---|---|
| Representative design | 150 kW motor | 605 m³/h | 60 m |
| Operating-scenario records | 128.9–133 kW | 630 m³/h | Not supplied here |
| Separate operating record | 134 kW | 859 m³/h | Not supplied here |
| Separate operating record | 128.9 kW | 760 m³/h | Not supplied here |
03 · CASE ANALYSIS
Compare the available interventions
Measure flow, suction/discharge pressures and electrical input; locate the operating point relative to pump/system curves and best-efficiency region.
Compare valve/control correction, impeller trim, variable speed, parallel-pump dispatch and replacement. Ideal affinity relations Q ∝ N, H ∝ N² and P ∝ N³ are screening tools, not verified savings.
04 · CASE ANALYSIS
Potential and service verification
The in-progress item considered approximately KRW 70 million/year benefit. A smaller motor by itself is not proof of a successful improvement.
Confirm required flow and head, chilled-water temperature, ΔT, coil service and chiller kW/RT. The final comparison includes chiller and pumping energy.
| Option | Engineering purpose |
|---|---|
| Control/valve correction | Reduce avoidable throttling |
| Impeller adjustment | Re-match the pump curve |
| Variable speed | Respond to varying flow/head demand |
| Pump dispatch | Select efficient parallel combinations |
| Pump replacement | Select actual required Q–H capability |
05 · CASE ANALYSIS
Hydronic-system lesson
Review bypass and low-ΔT causes before assuming that high circulation flow requires a larger pump. Demand-based differential-pressure control may improve existing assets without replacement.
Define the actual service boundary and evaluate lifecycle economics under the site’s demand profile.