CASE55 · Manufacturing · Chilled-water pump sizing

Re-matching chilled-water pumps to measured flow and head

Actual chilled-water demand and pump operating points are checked against original sizing. Control changes, impeller adjustment and pump replacement are compared at the required service level.

01 · CASE ANALYSIS

Original size versus current demand

Production, pipework and operating patterns can change after installation. A pump that once matched the design may later operate with unnecessary flow, head or throttling.

The source follow-up action was to select 5°C chilled-water pump specifications suited to actual use.

02 · CASE ANALYSIS

Source design and operating records

Representative design specifications for a 2,000 USRT 5°C chiller system were 150 kW motor, 605 m³/h flow and 60 m head.

Different source operating records show approximately 128.9–133 kW at 630 m³/h, and other records show 134 kW at 859 m³/h or 128.9 kW at 760 m³/h. These are different conditions, not a fabricated before/after pair.

Design and operating points
Source recordPowerFlowHead
Representative design150 kW motor605 m³/h60 m
Operating-scenario records128.9–133 kW630 m³/hNot supplied here
Separate operating record134 kW859 m³/hNot supplied here
Separate operating record128.9 kW760 m³/hNot supplied here

03 · CASE ANALYSIS

Compare the available interventions

Measure flow, suction/discharge pressures and electrical input; locate the operating point relative to pump/system curves and best-efficiency region.

Compare valve/control correction, impeller trim, variable speed, parallel-pump dispatch and replacement. Ideal affinity relations Q ∝ N, H ∝ N² and P ∝ N³ are screening tools, not verified savings.

04 · CASE ANALYSIS

Potential and service verification

The in-progress item considered approximately KRW 70 million/year benefit. A smaller motor by itself is not proof of a successful improvement.

Confirm required flow and head, chilled-water temperature, ΔT, coil service and chiller kW/RT. The final comparison includes chiller and pumping energy.

Alternatives
OptionEngineering purpose
Control/valve correctionReduce avoidable throttling
Impeller adjustmentRe-match the pump curve
Variable speedRespond to varying flow/head demand
Pump dispatchSelect efficient parallel combinations
Pump replacementSelect actual required Q–H capability

05 · CASE ANALYSIS

Hydronic-system lesson

Review bypass and low-ΔT causes before assuming that high circulation flow requires a larger pump. Demand-based differential-pressure control may improve existing assets without replacement.

Define the actual service boundary and evaluate lifecycle economics under the site’s demand profile.

APPLY TO YOUR SITE

Connect your operating data to an actionable energy strategy.

Discuss the measurement boundary, data quality, operating constraints and verification approach for your facility.