CASE14 · Manufacturing · Chillers and compressed air
Finding residual utility opportunities in an already efficient semiconductor plant
A proposal examines relationships among utility demand, supply, staging, setpoints and equipment performance after common operating improvements have already been implemented.
01 · CASE ANALYSIS
Operating challenge
The facilities already operated their utilities at a relatively high performance level. Additional opportunities required examining interacting variables rather than relying on a single equipment change or setpoint adjustment.
Demand-supply balance, load sharing, flow, temperature, pressure, valves, control logic and equipment combinations were considered together.
02 · CASE ANALYSIS
Proposal basis and site priorities
Two production sites had combined annual utility costs of approximately KRW 14.04 billion. The proposal estimated approximately KRW 634 million/year, or 4.5%, in further improvements.
Site B was prioritized because its larger utility cost and approximately KRW 476 million/year expected benefit gave it greater project significance. Rollout to other sites was proposed after verifying performance.
| Site | Annual utility cost | Expected rate | Expected saving |
|---|---|---|---|
| Site A | Approximately KRW 3.27 billion | 4.8% | KRW 158 million/year |
| Site B | Approximately KRW 10.78 billion | 4.4% | KRW 476 million/year |
| Combined | Approximately KRW 14.04 billion | 4.5% | KRW 634 million/year |
03 · CASE ANALYSIS
Optimization approach
The plan begins with field surveys, calibration of existing instruments, supplementary metering and data integration. Monitoring and data-quality validation support real-time performance diagnosis.
Operating measures include matching supply to production demand, balancing parallel equipment, selecting efficient units, reducing unnecessary bypass or concurrent operation, improving weak equipment and optimizing setpoints/control logic within process requirements. Operator training supports continued improvement.
04 · CASE ANALYSIS
Measurement and verification
At the priority site, the cooling proposal estimates 3.0% and KRW 206 million/year, while compressed air estimates 6.7% and KRW 270 million/year. These are pre-implementation expectations.
Verify against baselines incorporating production, cooling/airflow demand, weather and operating units. The report does not establish a confirmed 4.5% field saving or demonstrated AI performance.
| Utility | Annual cost | Expected rate | Expected saving |
|---|---|---|---|
| Chiller system | KRW 6.77 billion | 3.0% | KRW 206 million/year |
| Compressed air | KRW 4.00 billion | 6.7% | KRW 270 million/year |
05 · CASE ANALYSIS
Engineering lesson
When obvious improvements are exhausted, coordinated operating relationships can still identify opportunities. The proposal must remain distinct from results obtained after implementation.